ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
BODY HEIGHT | 3.187 INCHES NOMINAL |
BODY LENGTH | 10.125 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 4.125 INCHES NOMINAL |
BOSS HEIGHT | 0.125 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 7.750 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.687 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 7.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.687 INCHES NOMINAL |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 110.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 20000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 100.000 MINIMUM AT 200 PCT AND 300.000 MAXIMUM AT 200 PCT AND 30.000 MINIMUM AT 300 PCT AND 80.000 MAXIMUM AT 300 PCT AND 15.000 MINIMUM AT 400 PCT AND 45.000 MAXIMUM AT 400 PCT ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS MAXIMUM ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |