5925-00-024-0863 CIRCUIT BREAKER Index 5950-00-024-0866 TRANSFORMER,POWER

National Stock Number:
5925-00-024-0864

Federal Supply Class:
5925

National Item Identification Number:
000240864

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
65132205234THERMO JARRELL ASH CORP BAIRD DIV
659001CB105234THERMO JARRELL ASH CORP BAIRD DIV
72-317-1MG674193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
72-317-1NG674193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.240 INCHES MINIMUM AND 2.260 INCHES MAXIMUM
BOSS HEIGHT0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONRELAY TRIP THIRD LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP FIRST LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SECOND LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE3.5 AMPERES AC FIRST LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE3.5 AMPERES AC SECOND LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE500.0 MILLIAMPERES AC THIRD LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY3
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY8 THREADED STUD
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.300 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT14.000 OUNCES NOMINAL