ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY LENGTH | 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 1.500 INCHES MINIMUM AND 1.530 INCHES MAXIMUM |
BOSS HEIGHT | 0.130 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.515 INCHES MINIMUM AND 1.545 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.545 INCHES MINIMUM AND 1.675 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.5 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC AND 1000.0 DC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.000 INCHES NOMINAL |
NOMINAL THREAD SIZE | 3.0 MILLIMETERS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND 65.0 DC ALL LOCATIONS |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
SPECIAL FEATURES | TOGGLE HANDLE IS BLACK WITH WHITE MARKING |
TERMINAL TYPE AND QUANTITY | 4 THREADED STUD |
THREAD PITCH IN MILLIMETERS | 4.750 |
THREAD SERIES DESIGNATOR | ISO M |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.700 MINIMUM AT 125 PCT AND 12.000 MAXIMUM AT 125 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |